> > My real question:
> >
> > These UPSes have 3 load segments each. On the Compaq, I currently
> > use *2*. Is this the reason for its screaming? Does the total
> > load come from the three segments?
> >
>
> Fred, I'm betting the Compaq UPS is rated for 800VA per load segment.
> If this is true, then that means you are trying to supply 1650VA from
> two segments, which are rated for a total of 1600VA. Try
> moving some of
> the load to the third segment and see what happens.
>
> --